Sign In | Join Free | My hardware-wholesale.com |
|
Brand Name : Air Giant
Model Number : QMH20/80, QMH30/80
Certification : CAL,CMA,CNAS,ILAC-MRA,CCC
Place of Origin : China
MOQ : 1 set
Price : negotiation
Payment Terms : L/C , D/P, T/T, Western Union, Paypal, Credit card
Supply Ability : 300 sets per month
Delivery Time : 10-15 working days
Packaging Details : Plywood outer box with bubble bag or paper
Cylinder Volume : 80L
Capacity : 22.37kg, 33.56kg
Pattern of extinguishing : Enclosed flooding
Agent : IG541(52% Nitrogen, 40% Argon, 8% Carbon dioxide)
Working pressure : 20MPa, 30MPa
Max. working pressure : 23.2MPa, 36.6 MPa
System start mode : Electrical automatic, electrical manual, mechanical emergency star
Color : Red
Inert Gas Inergen IG541 Fire Extinguishing System Without Pollution For Battery Room
IG-541 Inergen gaseous is an environmentally friendly extinguishing agent, consisting of gases which are already present naturally in the earth's atmosphere. IG-541 is an inert gas, which means that it takes no part in the combustion process. IG-541 contains no liquid, is non-toxic and non-flammable.
IG-541 Inergen is a composite gas (52% Nitrogen, 40% Argon, 8% CO2) which is mixed and stored at a pressure of 300 bar. It is electrically non-conductive, which leaves no residue. At the correct design concentration, it is suitable for the protection of occupied areas.
IG-541 is a very effective fire extinguishing agent that can be used to protect a wide range of applications. It is suitable for class A, B, C, D and E fires, including risks with live electrical equipment. IG-541 extinguishing method is based on oxygen depletion.
Parameters
No. | Specification | Technical Parameter | |
1 | Working Pressure | 20MPa | 30MPa |
2 | Device Model | QMH20/80 | QMH30/80 |
3 | Capacity | 80Ltr | 80Ltr |
4 | Filling Capacity of Gas | 23.9kg | 33.2kg |
5 | Outside Diameter of Cylinder | Φ286mm | Φ286mm |
6 | Height of Cylinder | 1910mm | 1910mm |
7 | Spraying Time | ≤120s | ≤120s |
8 | Filling Rate | 0.299kg/L | 0.415kg/L |
9 | Power | DC24V/1.6A | DC24V/1.6A |
10 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20℃) | 6.0±1.0Mpa(20℃) |
11 | Condition of Reserving Room for Container | temperature: -20~50℃ | temperature: -20~50℃ |
12 | Max Working Pressure | 23.2MPa | 36.6MPa |
13 | Min Working Pressure | 18MPa | 27MPa |
System Composition
Storage cylinder group, storage cylinder group frame, nitrogen driving device, nitrogen driving device frame, the cylinder valve, liquid flow check valve, air flow check valve, electromagnetic starter, gas conveying pipeline, collecting pipe, choice valve, three links, reducer tee, reduceing elbow, flange, safety valve, pressure transmitter, pipe, nozzle, chemicals, fire detector, fire controller, sound and light alarm, alarm bell, gas light, emergency start / stop button, etc.
Application
Electronic computer room, a data processing center, telecommunications facilities, process control, expensive medical equipment, industrial equipment, library, museum and art gallery, clean room, anechoic chamber, emergency power facilities, flammable liquid storage area, etc.
The place where the fire is easy to happen, like paint-spraying production line, aging-electrical equipment, rolling machine, printing machine, oil switch, oil immersed transformer, melt impregnating tank, tank, large generators, drying equipment, cement pro duction process of pulverized coal, and the ship's engine room, cargo hold, etc.
Packages
We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.
![]() |
Inergen Ig541 Inert Gas Fire Suppression System 20MPa 30MPa Images |